DIG-LINE (Digital Line)
Issue 1 June 2005 949
S8300 / G700
● For the MM712 Media Module, the status of the EPF is sent uplink. Possible conditions are
EPF-on-ok, EPF-off, and EPF-no-load.
Table 325: Test #17 Station (Digital) Audits Test
Error
Code
Test
Result
Description / Recommendation
1 ABRT Switchhook audit timed out.
2 ABRT ID request fails, health bit returned from voice terminal is bad.
1. Make sure voice terminal is connected, and repeat the test.
2. If test fails, replace voice terminal and repeat test.
3ABRT
S8700 | 8710 / S8500: The EPF/PTC has detected an overcurrent condition.
1. For a TN754 vintage 13 or earlier Digital Line circuit pack, use test
location long.
● If Test #11 passes, then the EPF/PTC condition was cleared. Rerun
the Short Test Sequence.
● If Test #11 does not pass, follow the repair procedures described for
Test #11.
S8700 | 8710 / S8500 / S8300:
2. Look for Error Type 769 logged against DIG-LINE and follow the
procedures in the additional information. If any additional problems are
found, rerun the test.
4 ABRT Internal system error
1. Resolve any outstanding circuit pack or media module maintenance
problems.
2. Retry the command at 1-minute intervals up to 5 times.
5 ABRT Ringer update aborted due to station being in ready-for-service or
out-of-service state.
1 of 2