Communication Manager Maintenance-Object Repair Procedures
1214 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
1139 ABRT The packet bus in the PN where this EI board resides has a major alarm
against it. This test needs to use the alarmed PN’s packet bus.
1. Enter display alarms and display errors and resolve any
PKT-BUS alarms.
2. Retry the command.
1141 ABRT The Packet Interface circuit pack is out of service.
1. See PKT-INT (Packet Interface)
on page 1799.
1144 ABRT The PN’s packet bus has a major alarm against it. This test needs to use
the alarmed PN’s packet bus.
1. Enter display alarms and display errors and resolve any
PKT-BUS alarms.
2. Retry the command.
1394 ABRT The EI board is out of service and the test cannot be run. This condition is
due to a change in the EI board’s ability to communicate with the EI or SNI
circuit pack on the other end of the fiber.
1. Run Test #237 and check the Error Log for EXP-INTF Error Type 1281.
If Error Type 1281 is present or if Test #237 fails, see repair procedures
for Test #237, in Table 409: Test #237 Expansion Interface Neighbor
Query Test on page 1199.
1395 ABRT This test cannot be run on an EI circuit pack if it is part of the B-side PNC
and duplicated PNC is not enabled.
1. If this test needs to run on this EI circuit pack, enable PNC with change
system-parameters duplication.
2. Use set pnc lock to prevent the system from doing a PNC
interchange.
3. Repeat this test.
Table 413: Test #242 Expansion Interface Lightwave Transceiver Looparound (continued)
Error
Code
Test
Result
Description / Recommendation
3 of 6