BRI XID Test (#628)
This test checks the D-channel connection between the server and an endpoint or adjunct.
In this test, a D-channel XID frame is sent to the endpoint or adjunct over the point-to-point
signaling link. The test passes if the endpoint or adjunct responds with a layer-2
XID-RESPONSE frame
This test must be administered to not run in the Station Administration screen for ports on a
TN2208.
Table 245: Test #628 BRI XID
Error
Code
Test
Result
Description / Recommendation
1000 ABRT The BRI-SET, ASAI-ADJ, ATT-ADJ, LGATE-AJ, ATTE-AJ is busy. The test
cannot be executed at this time:
1. Pause momentarily (30 seconds) and re-execute at this time.
2. If this problem persists, escalate this problem.
Note: A BRI-PORT can also be busy. When using this for BRI-PORT/
ABRI-PORT tests, the words “BRI-SET, ASAI-ADJ, ATT-ADJ,” can be
changed to “BRI-PORT, ABRI-PORT, ATT-ADJ.”
1005 ABRT The endpoint is not administered to support XID testing.
1. If the endpoint documentation reflects support XID testing, use change
station extension and change the XID Testing field on the screen
to y.
1113 ABRT The signaling link between the switch and the endpoint is down.
1. Use test port location long to clear any errors that prevent
establishment of the signaling link.
2. Examine the results of the Signaling Link Status test (#626) that is run
as part of this command. If this test aborts or fails, follow the repair
procedure for Test #626.
3. If the XID test (#628) continues to abort, escalate the problem.
1139 ABRT The PN’s packet bus is out-of-service.
1. Follow the repair procedures for the packet bus.
2. After completing step 1, execute test port location long and
review the results of the BRI Port Local LAN Loop Around test (#618)
to verify the repair.