Communication Manager Maintenance-Object Repair Procedures
826 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
1018 ABRT The test was disabled via translation. You may want to determine why the
test has been disabled before you enable it.
1. Verify that the Maintenance Test field on the Trunk Administration
form is set to n. To enable the test, change the trunk administration and
enter y into the Maintenance Test field.
2. Repeat the test.
1020 ABRT The test did not run due to a previously existing error on the specific port or
a more general circuit pack error.
1. Examine Error Log for existing errors against this port or the circuit
pack and attempt to diagnose the previously existing error.
1412 ABRT This test does not execute on a G700/G350 Media Gateway.
2000 ABRT Response to the test request was not received within the allowable time
period.
1. Retry the command at 1-minute intervals up to 5 times.
2100 ABRT System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
2053 ABRT At least one of the following errors was found on the DS1 circuit pack: Loss
of signal (1281), Blue alarm (1793), Red alarm (2049), Yellow alarm (2305),
or Hyperactivity (1537).
Look for the previous error types in the Hardware Error Log, and follow the
procedures given in the appropriate DS1-BD or UDS1-BD maintenance
documentation for the listed error types.