Communication Manager Maintenance-Object Repair Procedures
562 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
1015 ABRT The ATM-EI circuit pack has not been busied out.
1. Busyout the ATM-Expansion Interface circuit pack, then repeat test
board location long .
1031 ABRT If the ATM Expansion Interface circuit pack is in a PN and is on the active
PNC, this test cannot be executed.
1. If PNC Duplication is enabled, attempt to make the standby PNC active
using reset pnc interchange.
2. If the PNC Interchange is successful, rerun the test.
1033 ABRT The ATM-EI circuit pack is absent.
1. Use list atm pnc to verify that switch recognizes the circuit pack.
2. Retry the command.
1139 ABRT The packet bus in the PN where this ATM-EI board resides has a major
alarm against it. This test needs to use the alarmed PN’s packet bus.
1. Resolve any PKT-BUS problems.
2. Retry the command.
1141 ABRT The Packet Interface circuit pack is out of service.
1. Resolve any PKT-INTF problems.
1394 ABRT The ATM-EI board is out of service and the test cannot be run. This
condition is due to a change in the ATM-EI board’s ability to communicate
with the ATM switch.
1. Run Test #241. If it does not pass, see repair procedures for
Expansion Interface 2-Way Transmission Test (#241)
.
1395 ABRT This test cannot be run on an ATM-EI circuit pack if it is part of the B-side
PNC and duplicated PNC is not enabled.
1. If this test needs to run on this ATM-EI circuit pack, enable PNC
duplication with the change system-parameters duplication
command.
2. Prevent the system from doing a PNC interchange by executing the
set PNC lock command.
3. Repeat this test.
Table 181: ATM Board Framer Loop-Around Test (#1260) (continued)
Error
Code
Test
Result
Description / Recommendation