Communication Manager Maintenance-Object Repair Procedures
1390 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
Network Connectivity (#1383)
This test is nondestructive.
This test passes if the Ethernet port is connected. It fails, with no error code or aux data, if no
electrical signal is detected.
Table 490: Test #1383 Network Connectivity
Error
Code
Test
Result
Description / Recommendation
None ABRT System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
1015 ABRT Port is not out of service.
1. Enter busyout board location to busyout the circuit pack.
2. Execute the command again.
2100 ABRT System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
FAIL The Ethernet cable is not connected.
PASS The Ethernet cable is connected.
0
NO
BOARD
The test could not relate the internal ID to the port (no board). This could
be due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Ensure that the board’s translations are correct.
2. If the board is not correctly administered, administer the IP Media
Resource interface.
If correctly administered, check the error log to determine whether the
board is hyperactive. If so, the board was shut down. Reseat the board
to reinitialize it.
3. If the board is correctly inserted and administered, enter busyout
board location.
4. Enter reset board location.
5. Enter release board location.
6. Enter test board location long.
This should re-establish the linkage between the internal ID and the port.