PKT-INT (Packet Interface)
Issue 1 June 2005 1823
NO
BOARD
The IPSI circuit pack’s Packet Interface module is assigned, but is not
detected as physically present.
1. If the IPSI circuit pack is present, replace it.
2. If an IPSI circuit pack is not present, insert a TN2312AP IPSI circuit
pack in the assigned slot, and rerun the test.
1 FAIL The Private Link Broadcast Loop-Around test failed. The Packet Interface
module on the IPSI circuit pack enters a fatal-fault state when this occurs,
and the Packet Interface maintenance software should put the Packet
Interface in a out-of-service state. By the time action is taken, the test
should abort with ABRT code 1137, and a demand reset should be used to
test the Packet Interface.
1. This may be the result of old firmware not supporting new software
operation. Verify the IPSI circuit pack’s firmware vintage and download
the new firmware if appropriate.
2. The firmware image on the IPSI circuit pack may have been corrupted.
Download the firmware image.
3. Retry the command.
4. If the same Error Code occurs, use reset packet-interface
location to reset the Packet Interface.
For further action, see the repair procedures in Table 674: Test #889
Reset Test on page 1836 for the Packet Interface Reset test (#889).
5. If the test continues to fail, replace the IPSI circuit pack.
Table 670: Test #885 Private Loop-Around Tests (continued)
Error
Code
Test
Result
Description / Recommendation
2 of 3