UDS1-BD (UDS1 Interface Circuit Pack)
Issue 1 June 2005 2431
Table 862: Test #142 Major Alarm Inquiry Test
Error
Code
Test
Result
Description / Recommendation
ABRT Internal system error
1. Retry the command at 1-minute intervals up to 5 times.
2000 ABRT Response to the test was not received within the allowable time period.
This may be due to hyperactivity. Error Type 1538 in the error log
indicates hyperactivity. The hyperactive circuit pack is out of service, and
one or more of the following symptoms may be exhibited.
1. The UDS1-BD tests (such as Test #138 and #139) are aborting with
Error Code 2000.
2. The tests run on the ports of this circuit pack are returning a
no-board result.
3. A busyout or a release command has no effect on the test
results.
4. A list config shows that the circuit pack and its ports are
properly installed.
When hyperactivity occurs, the circuit pack is isolated from the system,
and all of its trunks are placed into the out-of-service state. The system
will try to restore the circuit pack within 15 minutes. When no faults are
detected for 15 minutes, the UDS1 interface circuit pack is restored to
normal operation. Every UDS1 Interface trunk is then returned to the
in-service state. Hyperactivity is often caused by the associated facility. In
such a case, faults (such as slips, misframes, or blue alarms) would be
entered in the error log. In addition, many hardware errors would be
logged against the associated trunk circuits. If the facility is OK and the
error occurs again after 15 minutes, replace the circuit pack.
2100 ABRT Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
1 of 3