EXP-INTF (Expansion Interface Circuit Pack)
Issue 1 June 2005 1215
1407 ABRT This test cannot be run on an EI board that is on the active PNC because it
cannot be busied out. This error code indicates that PNC duplication is
enabled.
1. Attempt to perform a PNC interchange via reset pnc
interchange.
2. If the PNC interchange is successful, busyout the original EI circuit
pack via busyout board location (location of the original EI
board).
3. Retry the command.
2000 ABRT Response to the test was not received in the allowable time period.
1. Retry the command at 1-minute intervals up to 3 times.
2060 ABRT The link on the packet bus being used to perform the test has failed.
1. Retry the command at 1-minute intervals up to 3 times.
2. If the test continue to abort, enter display errors and resolve any
PKT-INT errors.
2100 ABRT Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 3 times.
2500 ABRT Internal system error
1. Retry the command at 1-minute intervals up to 3 times.
1 FAIL The test did not detect the test tone through the loop-around connection.
The packet portion of this test was not run since the circuit portion failed.
1. Test the active Tone-Clock on the PN that contains the defective EI
circuit pack to verify that dial tone is being supplied.
2. If the Tone-Clock is healthy, enter test board location long on
the EI circuit pack.
3. If this test continues to fail, replace the EI circuit pack or transceiver.
Then execute test board location long on the new EI circuit
pack.