Communication Manager Maintenance-Object Repair Procedures
336 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
Table 88: Test #78 Power Query Test
Error
Code
Test
Result
Description / Recommendation
1000 ABRT System resources required to run test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
100
2000
ABRT Response to the test request was not received within the allowable time
period.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to ABORT with error code 2000, check for
system powering problems with the PN’s A carrier. Resolve every
AC-POWER and CARR-POW (
S8700 IP: RMC-ENV) alarm. Repeat
the test.
3.
S8700 MC: If the test still ABORTs with error code 2000, check for
and resolve every MAINT (Maintenance circuit pack) error in a PN.
Repeat the test.
4. If the test still ABORTs with error code 2000, escalate the problem.
2029
2319
2320
2500
ABRT Internal system error
1 FAIL The cabinet is currently without AC power.
Note:
Note: For a J58890CE, skip to Procedures for a J58890CE.
Procedures for a Global MCC (J58890CH)
1. For a nominal holdover system if there is no AC power at the wall
outlet, have a qualified electrician restore power to the outlet. Power
should range from 170 to 264 VAC.
2. If there is AC power at the wall outlet, then there could be a problem
with the RM0850 rectifiers, BU3200A BIU (battery interface unit), or
battery. Resolve every alarm logged against the POWER MO, and
rerun the test. If the test still fails, the BIU may be defective. Check
the BIU. If the BOD alarm LED is on, replace the BIU. For
S8700 MC,
if the BOD LED is off and the BOK LED is on, then a PN’s
Maintenance circuit pack may be incorrectly reporting the problem.
Resolve every alarm against these MOs, and rerun the test.