CAB-TEMP (Cabinet Temperature)
Issue 1 June 2005 753
CAB-TEMP (Cabinet Temperature)
G650
The MO CAB-TEMP monitors the G650 and the 655A for the following:
● The power supply
- Inlet temperature
- Hot spot temperature status
- Fan speed
- Fan alarm lead
● The G650 carrier exhaust temperature
The serial bus is used by the TN2312BP IPSI to obtain this information from each power supply
in a G650 media gateway. There is only one outlet temperature sensor and fan assembly in a
G650, so information obtained from dual power supplies (slot 0 and 15) is redundant.
Refer to Figure 115: G650 Cabinet Environmental Hardware Components
on page 1959 for
further information.
Note:
Note: Fan/filter replacement procedures for the CMC1 and G600 media gateways are
to be found under Variable-speed fans
in Maintenance Procedures (03-300192).
Error log entries and test-to-clear values
MO name (in
alarm log)
Alarm
level
Initial SAT command to
run
Full name of MO
CAB-TEMP MIN test board location Cabinet Temperature
CAB-TEMP MAJ test board location Cabinet Temperature
Table 259: CAB-TEMP Error Log Entries
Error
Type
Aux
data
Associated test Alarm
level
On/Off
board
Test-to-clear value
1 (a) Power supply
temperature test (#1537)
MIN OFF test enviroment location
test board location
257 (b
) Power supply
temperature test (#1537)
MIN ON test enviroment location
test board location