RING-GEN (Analog Ring Generator)
Issue 1 June 2005 1945
Analog Ring Generator Query Test (#118)
The Analog Ring Generator Query test requests the active Tone-Clock circuit pack to check the
ringing voltage. The Tone-Clock circuit pack replies with PASS if the ringing voltage is adequate
to ring the analog phones. If not, the active Tone-Clock circuit pack replies with a FAIL.
2000 ABRT Response to the request was not received within the allowable time
period.
1. Look for TDM-CLK errors and alarms. Resolve every other
Tone-Clock problem first.
2. Rerun the test.
PASS The active Tone-Clock has successfully been enabled to monitor the
ringing voltage level.
Table 715: Test #117 Analog Ring Generator Initialization Test (continued)
Error
Code
Test
Result
Description / Recommendation
2 of 2
Table 716: Test #118 Analog Ring Generator Query Test
Error
Code
Test
Result
Description / Recommendation
1
1000
1001
1003
1115
2012
2100
ABRT Could not seize the resources to run the test. Other maintenance is
running on the active Tone-Clock circuit pack.
1. Wait for the green LED on the active Tone-Clock circuit pack to go out.
2. Use status port-network to determine the active Tone-Clock
circuit pack.
3. Rerun the test. If the test aborts again, see TDM-CLK (TDM Bus
Clock) on page 2252.
2000 ABRT Response to the request was not received within the allowable time
period.
1. Look for TDM-CLK errors and alarms. Resolve every other
Tone-Clock problem first.
2. Rerun the test.
1 of 4