Communication Manager Maintenance-Object Repair Procedures
1762 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
1001 ABRT System resources required to run this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
1002 ABRT The system could not allocate time slots for the test. The system may be
under heavy traffic conditions or it may have time slots out-of-service due
to TDM-BUS errors.
1. If the system has no TDM-BUS errors and is not handling heavy
traffic, repeat the test at 1-minute intervals up to 5 times.
1003 ABRT The system could not allocate a tone receiver for the test. The system
may be oversized for the number of tone detectors present or some tone
detectors may be out-of-service.
1. Resolve any TTR-LEV errors.
2. Resolve any TONE-PT errors.
3. If neither condition exists, retry the command at 1-minute intervals up
to 5 times.
1004 ABRT The port was seized by a valid call during the test. The test has been
aborted.
1. Use display port location to determine the data module
extension. Use status data module with the extension number to
determine the service state of the data module. If the data module is
in use, wait until the port is idle before retesting.
G700:
1412
ABRT This test does not execute on a G700 media gateway.
2000 ABRT Response to the test request was not received within the allowable time
period.
1. Retry the command at 1-minute intervals up to 5 times.
:2001 ABRT System resources required to run this test are not available.
1. Retry the test at one-minute intervals a maximum of 5 times.
2100 ABRT System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
2500 ABRT Internal system error
1. Retry the command at 1-minute intervals up to 5 times.
Table 652: Information and Control Channel Local Loop Test (continued)
Error
Code
Test
Result
Description / Recommendation