Communication Manager Maintenance-Object Repair Procedures
2062 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
102 FAIL The SNI circuit pack cannot communicate with the SNI in slot 2 over the
circuit path.
1. Fix any on-board SNI-BD errors against this SNI and the SNI in slot 2.
Use display errors to find any SNI-BD errors and check
display alarms to see if the errors have on-board alarms. Follow
the repair procedures for SNI-BD.
2. Use display errors to check the error log for other SNI circuit
packs with SNI-PEER Error Type 1. If other SNI circuit packs have
SNI-PEER Error Type 1, then replace the SNI in slot 2. Replacing an
SNI may be service interrupting. See SNI-BD (SNI Circuit Pack)
on
page 2046 for the procedure for replacing an SNI.
3. If other SNI circuit packs do not have SNI-PEER Error Type 1 errors,
the problem could be at either of the peer SNI boards. It is arbitrary as
to which SNI is replaced first. Proceed as follows:
4. Replace this SNI.
5. Replace the SNI in slot 2.
103 FAIL The SNI circuit pack cannot communicate with the SNI in slot 3 over the
circuit path.
1. Fix any on-board SNI-BD errors against this SNI and the SNI in slot 3.
Use display errors to find any SNI-BD errors and check
display alarms to see if the errors have on-board alarms. Then
follow the repair procedures for SNI-BD.
2. Use display errors to check the error log for other SNI circuit
packs with SNI-PEER Error Type 257. If other SNI circuit packs have
SNI-PEER Error Type 257, then replace the SNI in slot 3. Replacing
an SNI may be service interrupting. See SNI-BD (SNI Circuit Pack)
on
page 2046 for the procedure for replacing an SNI.
If other SNI circuit packs do not have SNI-PEER Error Type 257 errors, the
problem could be at either of the peer SNI boards. It is arbitrary as to which
SNI is replaced first.
3. Replace this SNI.
4. Replace the SNI in slot 3.
Table 749: TEST #755 SNI Circuit Path Test (continued)
Error
Code
Test
Result
Description / Recommendation