G700 Traps and Resolutions
Issue 1 June 2005 305
G700 Traps and Resolutions
Although these alarms can be viewed from the primary server, they are normally resolved from
within the G700 Media Gateway. The G700 generates the following traps. Follow the error
resolution procedures in Table 83: G700 Alarms (SNMP Traps) to the Primary Media Server
on
page 305 to resolve errors indicated by these traps.
Table 83: G700 Alarms (SNMP Traps) to the Primary Media Server
Event
ID
Trap
#
Alarm
Level
Description / Recommendation
1 2 WRN cmgMultipleFanFault — At least two G700 fans have been
operating at less than 90% of their nominal speed for >= 5 minutes.
(This may be an early warning of overheating.)
1. Verify there are faults in the system. Use the Avaya G700
Media Gateway Processor (MGP) Command Line Interface
(CLI) command show faults to display any faults on the
G700.
2. If there is a fan/temperature fault, check to see if the fans are
working, and/or if there is sufficient space around the G700 for
air circulation.
3. Maintenance software monitors voltages applied to the Media
Modules and other components of the G700, and compares
these to the general power supply unit (PSU) status bit. If none
of these voltages are out of tolerance, but the PSU status
indicates failure, this generates the fan fault, which will be
indicated in the show faults command output. Replace the
entire G700. Fans and the PSU are not field replaceable.