RING-GEN (Analog Ring Generator)
Issue 1 June 2005 1947
FAIL
(
cont’d)
Since the test still fails, the ring generator is defective.
a. If the reset button on the ring generator is out, press it in.
b. Originate calls to several analog stations on different port circuit
packs in different carriers in the affected port network.
c. If called stations ring, the fault is cleared. Proceed to Step d. If no
stations ring, replace the ring generator.
d. Rerun the test. If the test still fails, proceed to Step 7.
1. The active Tone-Clock may be faulty and incorrectly reporting the
level of the ringing voltage. Replace the active Tone-Clock, and rerun
the test. See TONE-BD (Tone-Clock Circuit)
on page 2327 for details
on replacing the Tone-Clock. Rerun the test.
Table 716: Test #118 Analog Ring Generator Query Test (continued)
Error
Code
Test
Result
Description / Recommendation
3 of 4