CLAN-BD (Control LAN Circuit Pack)
Issue 1 June 2005 801
Circuit Pack Restart Test (#252)
This test is destructive.
Execute this test (not part of either short or long demand test sequence) to reset the circuit pack
only if there are PPCPU errors. This test fails if the circuit pack does not return to a sane state
after being reset. The circuit pack resets through the SAKI Sanity test (#53).
Table 271: Test #252 Circuit Pack Restart Test
Error
Code
Test
Result
Description / Recommendation
None ABRT Could not allocate the necessary system resources to run test.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the problem persists, escalate the problem.
1015 ABRT Port is not out-of-service.
1. Busyout the circuit pack (busyout board location).
2. Retry the command at 1-minute intervals up to 5 times.
3. If the problem persists, escalate the problem.
2100 ABRT Could not allocate the necessary system resources to run test.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the problem persists, escalate the problem.
1, 2 FAIL The circuit pack failed to reset.
1. Retry command at 1-minute intervals up to 5 times.
2. If the problem persists, pull out and reseat the circuit pack.
3. If the problem persists, replace the circuit pack.
PASS The circuit pack initialized correctly.