Communication Manager Maintenance-Object Repair Procedures
340 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
AC Power Query Test (#78)
AC Power Query Test (#78) is not valid for DC-powered cabinets and should always abort or
pass.
S8700 IP will always abort.
Table 91: Test #78 Power Query Test
Error
Code
Test
Result
Description / Recommendation
1000 ABRT System resources required to run test are not available.
100
2000
ABRT Response to the test request was not received within the allowable
time period.
1. Retry the command at 1-minute intervals up to 5 times.
2029
2319
2320
2500
ABRT Internal system error.
S8700 MC:
1. Retry the command at 1-minute intervals up to 5 times.
S8700 MC
Any
FAIL A PN’s Maintenance circuit pack is incorrectly reporting an AC power
problem. If this test fails, there is a problem with a Maintenance circuit
pack. Replace the suspected circuit pack, and run the test again.
S8700 MC PASS Since this test is invalid for DC-powered cabinets, this result simply
indicates that a PN’s Maintenance circuit pack is handling this test
properly.