Server Alarms
92 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
1. These events will degrade the server’s state of health.
System Technician-Demanded Tests:
Descriptions and Error Codes
This MO provides no on-demand tests for system technicians.
Back to: Hardware MOs
Server-related alarms
UPS Alarms to the Media Server
S8700 | 8710 / S8500 / S8300
Table 26: UPS Alarms to the Media Server on page 92 describes the server’s UPS-related
alarms and their troubleshooting procedures.
Trap (3) –
upsAlarmGeneralFault
#27
#1,ACT,UPS,A,27,WRN,Miscellaneous trap, e.g., bad
battery
(For troubleshooting procedures, see Event #27
on
page 95)
Table 25: Enterprise-Specific UPS Traps to Server (continued)
SNMP Trap from UPS Event
ID
Definition of Trap
4 of 4
Table 26: UPS Alarms to the Media Server
Event
ID
Alarm
Level
Alarm Text, Cause/Description, Recommendation
1–8 MAJ “upsEstimatedMinutesRemaining” — UPS does not have an AC-power
source.
1. Restore AC power to the UPS.
12 MAJ “upsAlarmShutdownPending” — A shutdown-after-delay countdown is
underway (i.e., the UPS has been commanded off).
1. Stop countdown timer. (Can be done via SNMP messages.)
13 MAJ “upsAlarmShutdownImminent” — The UPS will turn off power to the load in
< 5 seconds.
1. Restore AC power to the UPS.
1 of 4