Communication Manager Maintenance-Object Repair Procedures
1770 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
1000 ABRT Could not get translation information for port.
1. Verify that port circuit is administered.
2. Wait one minute and attempt the test again.
3. If the test continues to abort and the port is not in use, escalate the
problem.
1005 ABRT This test is not applicable to the given hardware configuration.
1. This abort message can be ignored.
1020 ABRT Internal Software Error.
1. Retry the command at one-minute intervals a maximum of 5 times.
1030 ABRT Internal software group identifier for data module not valid.
1. Verify that port circuit is administered correctly.
2. If administration data correct, escalate the problem.
1031 ABRT Extension number not valid.
1032 ABRT Extension number not correct length.
1. Verify that the data module extension is administered correctly.
2. If the administration data is correct, escalate the problem.
1071 ABRT No auxiliary port on Netcon circuit pack available to test with.
1. Check that the Netcon data channels are administered (the list
data-modules command should show at least one Netcon-type
data module).
2. Test the Network Control (Netcon) circuit pack using the test
data-module command for the Netcon circuit pack.
3. If administration data is correct, escalate the problem.
Table 654: Test #175 Data Module Internal Loop-Around Test (continued)
Error
Code
Test
Result
Description / Recommendation