SNI-BD (SNI Circuit Pack)
Issue 1 June 2005 2093
Packet Neighbor Link Test (#767)
This test is nondestructive.
This test checks the packet path of the neighbor circuit pack and the peer circuit packs. A
packet is sent from the SNI being tested to the peer SNIs and to the neighbor EI or SNI. If the
other EI or SNI sends the same data back in the packet, this test passes. Otherwise, this test
fails.
Table 754: TEST #767 Packet Neighbor Link Test
Error
Code
Test
Result
Description / Recommendation
2100 ABRT Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 3 times.
2300 ABRT The downlink message necessary to run this test could not be sent.
1. Retry the command at 1-minute intervals up to 3 times.
2301 ABRT The software timer could not be set before sending the downlink message
necessary to run this test.
1. Retry the command at 1-minute intervals up to 3 times.
2302 ABRT Software received incorrect message data from the SNI circuit pack.
1. Retry the command at 1-minute intervals up to 3 times.
2303 ABRT The SNI circuit pack responded that the software test requested is invalid.
1. Retry the command at 1-minute intervals up to 3 times.
2304 ABRT SNI firmware is not able to run the test. For this particular test, the SNI
circuit pack must be able to communicate with its neighbor.
1. Verify that the SNI can communicate with its neighbor by checking the
yellow LED of the SNI to make sure the SNI is in frame, or by running
test board for the SNI and checking test 989 for fiber out-of-frame.
If the results of Test 989 indicate that the fiber is out-of-frame, follow
the recommendation associated with the test failure. If a DS1
converter complex exists on the fiber link, enter display errors
and follow the repair procedures for any DS1C-BD and DS1-FAC
entries.
2. Retry the command at 1-minute intervals up to 3 times.
1 of 12