SNI-BD (SNI Circuit Pack)
Issue 1 June 2005 2089
140 FAIL The SNI is physically connected to a DS1C but is not administered to be
connected to a DS1C.
Either add the DS1 converter complex to the fiber that this SNI is
associated with by:
1. Use list fiber-link to determine the fiber associated with the
SNI.
2. Use remove fiber-link to remove the fiber.
3. Use add fiber-link to add the fiber back, and administer the DS1
converter complex.
Or:
4. Remove the DS1C connection, and connect the SNI directly to its
administered fiber endpoint.
5. Verify that the fiber-optic and metallic cable connections are installed
as administered by entering list fiber-link.
PASS The administered data and the circuit packs the SNI can communicate with
match.
0NO
BOARD
No board was detected by the test.
1. Check that board is properly translated and inserted.
2. Run the test again. If it fails, reset the board. An SNI should be reset
instead of reseating the circuit pack. The reset board command
should almost never be used on an SNI. It may be necessary to use
reset board if the SNI circuit pack gets into a mode where it cannot
communicate with software. If an SNI with active errors and alarms is
reset, the errors and alarms may take a while to come back, therefore
reset board can mask real problems.
3. Run the test again. If it fails, the ID chip on board may be bad.
Replace the board and retest.