Communication Manager Maintenance-Object Repair Procedures
1524 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
Notes:
a. Error Type 0: Run the short test sequence first. If every test passes, run the long test
sequence. Refer to each test’s description and follow its procedures.
b. Error Type 1: the circuit pack has totally stopped functioning or is not fully administered.
The alarm is logged about 15 minutes after the circuit pack has been removed or 11
minutes after the SAKI test (#53) fails.
To be fully administered, a MAPD circuit pack must:
Have an entry in the circuit plan (change circuit-pack)
Be administered (add ds1 location)
Be physically inserted into the correct slot
If the circuit pack has an entry in the circuit plan and the other two conditions are not met, a
MINOR alarm is logged. To resolve the error:
Make sure the circuit pack is properly administered and that a functioning MAPD circuit
pack is inserted in the correct slot
or
Completely remove the MAPD-BD from the system:
1. Shut down Windows 2000. See Shutting Down NT on the TN802
on page 1529.
2. Remove any administered DS1 trunks, access endpoints, or PRI endpoints associated
with the circuit pack from their respective trunk groups.
3. Remove the DS1 (remove ds1 location) and circuit pack (change
circuit-pack location) administration.
3841 (r
) 4358
3842 (s
) 46097
3843 (t
) 46081
3999 (u
) Any None
1. If ports are assigned to the circuit pack, then a minor alarm is raised. If no ports are assigned to the circuit
pack, then a warning alarm is raised. The alarm is raised after the circuit pack has been missing for a
period of 15 minutes. Warning alarms are also raised against any ports administered on the circuit pack.
2. Minor alarms on this MO may be downgraded to warning alarms based on values set in set options.
3. Major alarms on this MO may be downgraded to minor or warning based on values set in set options.
Table 550: MAPD (TN802) Error Log entries (continued)
Error
Type
Aux
Data
Associated Test Alarm
Level
On/Off
Board
Test to Clear Value
3 of 3