Analog Ring Generator Initialization Test (#117)
The Analog Ring Generator Initialization test sends a request to the active TN768, TN780,
TN2182 Tone-Clock or TN2312AP IPSI circuit pack’s Tone-Clock circuit to monitor the voltage.
The Tone-Clock responds with an error if the ringing voltage falls too low.
Order of Investigation Short Test
Sequence
Long Test
Sequence
D/ND
1
1. D = Destructive, ND = Nondestructive
Analog Ring Generator Initialization test (#117) X X ND
Analog Ring Generator Query test (#118) X X ND
Single-Carrier Cabinet Power Query test (#79) (a
)X X ND
Emergency Transfer Query test (#124) (b
)XXND
External Alarm Lead Query test (#120) (c
)XXND
Table 715: Test #117 Analog Ring Generator Initialization Test
Error
Code
Test
Result
Description / Recommendation
1
1000
1001
1003
1115
2012
2100
ABRT The system software is unable to determine the active Tone-Clock circuit
pack, unable to allocated the resources necessary to run the test, or
unable to send a down link message.
1. Wait for the green LED on the active Tone-Clock to go out.
2. Use status port-network to determine the active Tone-Clock
circuit pack.
3. Rerun the test. If the test aborts again, see TDM-CLK (TDM Bus
Clock) on page 2252.