MAINT (PN’s Maintenance Circuit Pack)
Issue 1 June 2005 1505
PN Maintenance Circuit Pack Serial Link
Test (#337)
This test is destructive.
This test checks the serial link from the standby EI or standby IPSI circuit pack to the PN’s
Maintenance circuit pack. If there is no standby link, or the standby link is down at the time of
the test, this test aborts.
Note:
Note: The status of the link changes to “down” when the standby EI or standby IPSI
circuit pack begins initialization tests (for example, after being reset). The link
status updates at the conclusion of these tests.
FAIL The hardware vintage of the PN’s Maintenance circuit pack does not
support battery holdover for all carriers.
This failure indicates that the cabinet administration is set for battery
holdover for all carriers.
1. Verify cabinet administration, make sure that the battery holdover
feature is administered correctly (That cabinet administration is not
set for battery holdover for all carriers.).
2. Retry the command at 1-minute intervals up to 5 times.
PASS The cabinet administration shows battery holdover for A carrier only. Also,
the hardware vintage of the PN’s TN775D Maintenance board is correct.
Table 541: TEST #303 PN Maintenance Circuit Pack Sanity Maze Test (continued)
Error
Code
Test
Result
Description/ Recommendation
2 of 2
Table 542: Test #337 PN Maintenance Circuit Pack Serial Link Test
Error
Code
Test
Result
Description / Recommendation
1000 ABRT System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
2029 ABRT Internal system error.
1. Retry the command at 1-minute intervals up to 5 times.
1 of 2