Communication Manager Maintenance-Object Repair Procedures
1750 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
0NO
BOARD
The test could not relate the internal ID to the port (no board). This
could be due to incorrect translations, no board is inserted, an incorrect
board is inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use list
config, and resolve any problems that are found.
2. If the board was found to be inserted correctly, enter busyout
board location.
3. Enter the reset board location command.
4. Enter the release board location command.
5. Enter test board location long.
This should re-establish the linkage between the internal ID and the
port. If not, ensure that there is a valid board inserted.