Communication Manager Maintenance-Object Repair Procedures
766 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
S8700 |
8710
S8500:1
(
cont’d)
FAIL
(
cont’d)
If some of the fans are running and some are not:
1. Replace the defective fans. If every fan can then be started, wait 5
minutes and rerun the test. If the test fails again, proceed to the next
step.
2. Remove all six white 5-pin connectors on the front and back of the fan
assembly. This will cause every fan to run at high speed and the alarm
to be cleared.
S8700 MC: If the alarm does not clear, a PN’s Maintenance circuit pack
is incorrectly reporting the problem. Check for and resolve every error
against MAINT, and then rerun the test.
3. One at a time, replace the 5-pin connectors and check to see if the
alarm recurs. Replace each fan whose reconnection causes a
recurrence of the alarm.
Table 264: Test #122 Cabinet Temperature Query Test (continued)
Error
Code
Test
Result
Description / Recommendation
4 of 7