Communication Manager Maintenance-Object Repair Procedures
1890 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
Power supply voltage test (#1536)
The TN2312BP IPSI scans the status of each 655A power supply on the serial bus every 5
seconds. This test returns the status of the most recent scan of the 655A DC output voltages.
PASS The power supply detection test passes.
NO
BOARD
Power supply is administered but not detected.
1. Verify that the power supply is plugged in.
2. Replace the power supply.
1. It is unlikely that these failure codes will occur when redundant power supplies are present because each
power supply is measuring the backplane voltage rather than the power supply voltage.
Table 689: Test 1535 power supply detection test (continued)
Error
code
Test
result
Description and recommendation
3 of 3
Table 690: Test #1536 power supply voltage
Error
code
Test
result
Description and recommendation
1000 ABRT There is an internal software error.
1. Retry the command.
2. Escalate the problem if the test continues to abort.
1035 ABRT The port network is not available.
1. Verify with status port-network nn command.
2028 ABRT There is a problem communicating with the environmental maintenance
firmware.
1. Run test maintenance nn
2100 ABRT The system could not allocate resources.
1. Repeat the command at one-minute intervals 1 to 3 times.
2. Escalate the problem if the test continues to abort.
2319 ABRT The EPN is out of range.
1 of 3