MET-LINE (MET Line)
Issue 1 June 2005 1567
Port Diagnostic Test (#35)
This test checks a port's battery feed circuitry. The battery feed circuitry is tested for proper
battery voltage by testing the switchhook state. In response to the test message, the on-board
firmware terminates the line and checks for switch-hook presence. The termination is then
removed, and a check is made for no switch-hook presence. The MET set must be on-hook for
the test to execute.
0NO
BOARD
The test could not relate the internal ID to the port (no board). This could
be due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use list
config and resolve any problems that are found.
2. If the board was found to be inserted correctly, enter busyout board
location.
3. Enter the reset board location command.
4. Enter the release board location command.
5. Enter test board location long. This should re-establish the
linkage between the internal ID and the port. If this is not the case,
check to ensure that there is a valid board inserted.
Table 578: Test #6 NPE Crosstalk Test (continued)
Error
Code
Test
Result
Description / Recommendation
4 of 4
Table 579: Test #35 Port Diagnostic Test
Error
Code
Test
Result
Description / Recommendation
ABRT Internal system error.
1. Retry the command at 1-minute intervals up to 5 times.
1 of 3