Communication Manager Maintenance-Object Repair Procedures
2134 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
If the alarm is MAJOR:
Check connections between the Stratum-3 clock and the switch.
If there are no loose connections, use the Stratum-3 Wiring Guide and check that the
wiring installation is correct.
After reconnecting the loose connection or correctly rewiring it, clear the alarm by issuing
disable synchronization-switch, followed by enable
synchronization-switch.
Wait 1 minute, then run status synchronization.
If Maintenance Name on the status screen shows “STRAT-3,” then the problem is
resolved.
If the Standby Tone-Clock circuit pack became active:
Check the connection between the Stratum-3 clock and the TN780 Tone-Clock circuit
pack from which the system has just switched.
If there are no loose connections, then, replace the circuit pack containing the TN780
Tone-Clock circuit pack.
Before switching back to the new TN780 Tone-Clock circuit pack, use test
tone-clock location long to check that the Tone-Clock is receiving a signal from
the Stratum-3 clock.
If every test passes, switch to the new Tone-Clock circuit pack using set tone-clock
location override.
If Test #651 fails, then the original TN780 Tone-Clock circuit pack should be reinserted,
and the cable between the Stratum-3 clock and the TN780 Tone-Clock circuit pack
should be replaced.
If Test #651 continues to fail, then escalate the problem.
If slip alarms exist after following the repair procedures for any of the previous cases,
clear the slip alarms by running test board clear. See Table 765: Timing Slip Error
Types on page 2133 for a list of circuit packs and associated slip error log entries.
This error indicates that the Tone-Clock circuit pack in the master port network is not a
TN780. If duplicate Tone-Clock circuit packs exist in the master port network, this error
may mean that one or both Tone-Clock circuit packs are not TN780s. Verify that the
Tone-Clock(s) in the master port network are TN780s.
h. Error Type 1281: this Error Type corresponds to FAIL code 32 of the Stratum-3 Clock Alarm
Query test (#649): every clock unit failed.
i. Error Type 1537: An OFF-BOARD alarm on the Stratum-3 clock, indicates a DS1 facility
problem; an ON-BOARD alarm indicates a fault in either the Stratum-3 clock or the
connection between the Stratum-3 clock and the switch. If the Stratum-3 clock cannot be
referenced and the local oscillator on the TN780 Tone-Clock circuit pack must serve as the
reference, a Major alarm is raised. Otherwise, a Minor alarm is raised.