POWER
Issue 1 June 2005 1877
8
(
cont’d)
FAIL
(cont’d)
d. If there is an alarm and every LED is OK (PWR OK and
BOK) on the rectifier modules and the BIU (Battery Interface
Unit), make sure the BIU and the RM0850 rectifiers are
seated properly (plugged in). If the BOK LED on the BIU is
OK, check the number of rectifiers serving this cabinet:
No. of carriers/cabinet
No. of rectifiers/cabinet
1 2
2 3
3 3
4 4
5 4
If the number of rectifiers is correct replace the maintenance
circuit pack in the PN.
10 FAIL Error codes 2 and 8 have occurred. Refer to these descriptions. Also,
refer to this test’s description for Error Code 14.
12 FAIL Error codes 4 and 8 have occurred. Refer to these descriptions. Also,
refer to this test’s description for Error Code 14.
14 FAIL Error codes 2, 4, and 8 have occurred. Refer to these descriptions.
This could also indicate that the detection logic on the PN’s MAINT
(Maintenance) circuit pack is defective. Such an error will not be
detected by the respective maintenance. If many environment tests are
failing, replace the suspect circuit pack (depending on system
configuration).
PASS The PN’s Maintenance circuit pack has reported that the status of
Battery and Battery Charger is good.
Table 684: Test #5 Battery and Battery Charger Query Test (continued)
Error
Code
Test
Result
Description / Recommendation
5 of 5