CLAN-BD (Control LAN Circuit Pack)
Issue 1 June 2005 805
Packet Interface Test (#598)
This nondestructive test checks the packet-bus interface circuitry on the C-LAN circuit pack.
Test failure indicates faulty circuit pack.
1–10 FAIL The circuit pack detects LAPD frame errors. The error code indicates the
value of the on-board error counter.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to fail, execute the Packet Interface test (#598)
(test board location long).
3. If the Packet Interface test (#598) fails, see PKT-BUS (Packet Bus)
on
page 1790 for repair procedures.
PASS Circuit pack detects no errors.
Table 274: Test #597 Invalid LAPD Frame Error Counter Test (continued)
Error
Code
Test
Result
Description / Recommendation
2 of 2
Table 275: Test #598 Packet Interface Test
Error
Code
Test
Result
Description / Recommendation
2000 ABRT Did not receive circuit pack test response within the allowable time period.
1. Retry command at 1-minute intervals up to 5 times.
2. If the problem persists, reset the circuit pack with reset board
location.
3. If the problem persists, replace the circuit pack.
2012 ABRT Could not allocate the necessary system resources to run test.
1. Retry the command at 1-minute intervals up to 5 times.
2100 ABRT Internal system error.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the problem persists, escalate the problem.
1 of 2