CAB-MTCE (Media Gateway Maintenance)
Issue 1 June 2005 747
1982 ABRT The board being tested is NOT a TN2312BP IPSI or later.
1. Insert a TN2312BP IPSI circuit pack.
1986 ABRT The TN2312BP IPSI failed to set emergency transfer to AUTO at
initialization.
1. Enter reset maintenance
2. If the reset maintenance command aborts again enter set emergency
command to see if emergency transfer can be activated or deactivated.
3. If the reset maintenance command continues to abort escalate the
problem.
2000 ABRT The response to a query was not received in the time allowed.
1. Run reset maintenance
2. Escalate the problem if the test continues to abort.
2500 ABRT An internal operation failed (Possible unknown cabinet type).
1. Repeat the command at one-minute intervals 1 to 3 times.
2. Escalate the problem if the test continues to abort.
1 FAIL The TN2312BP IPSI environmental maintenance initialization failed.
1. Repeat the command at one-minute intervals 1 to 3 times.
2 FAIL The TN2312BP IPSI failed a sanity test.
1. Run reset maint command.
2. If the problem persists, replace the circuit pack.
PASS Environmental maintenance has been enabled and passes a sanity test.
Table 254: Test #1545 Reset test (continued)
Error
code
Test
result
Description and recommendation