MAPD-BD (MAPD Interface Circuit Pack TN802)
Issue 1 June 2005 1533
SAKI Sanity Test (#53)
This test is destructive.
This test resets the circuit pack. The test is highly destructive and can only be initiated by a
system technician-demanded reset board location.
Table 554: Test #53 SAKI Sanity Test
Error
Code
Test
Result
Description / Recommendation
None ABRT System resources required for this test are not available.
1. Retry reset board at 1-minute intervals up to 5 times.
1015 ABRT Port is not out-of-service.
1. Busyout the circuit pack (busyout board location).
2. Execute reset board.
2100 ABRT System resources required for this test are not available.
1. Retry reset board at 1-minute intervals up to 5 times.
1 FAIL The circuit pack failed to reset.
2 FAIL The circuit pack failed to restart.
1. Execute reset board.
2. If the problem persists, replace the circuit pack.
PASS The circuit pack initializes correctly.
1. Run the short test sequence.
0NO
BOARD
The test could not relate the internal ID to the port (no board). This could
be due to incorrect translations, no board is inserted, an incorrect board
is inserted, or an insane board is inserted.
1. Ensure that the board translations are correct. Use add ds1
location to administer the MAPD interface if it is not already
administered.
2. If the board was already administered correctly, check the error log
to determine whether the board is hyperactive. If so, the board was
shut down. Reseating the board re-initializes it.
3. If the board was inserted correctly, enter busyout board.
4. Enter the reset board command.
5. Enter the release board command.
6. Enter the test board long command.
This should re-establish the linkage between the internal ID and the port.