Communication Manager Maintenance-Object Repair Procedures
1134 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
EMG-XFER (Emergency Transfer)
S8700 | 8710 / S8500
S8700 | 8710 / S8500
Emergency Transfer (SCC Cabinets)
The system provides the ability to cut designated analog phones through to CO trunks if the
switch cannot provide even minimal phone service. This ability is known as Emergency
Transfer. The EMG-XFER MO tracks the control of Emergency Transfer. There is one
EMG-XFER MO for the port network. Emergency Transfer can be controlled by the system or
can be manually controlled via the Emergency Transfer switch located on the Maintenance
(TN775) circuit pack. A manual ON position (up) generates a Major alarm. A manual OFF
position (down) generates a Warning alarm. Unless a technician is currently working on the
system, the switch should be left in the auto position.
Error Log Entries and Test to Clear Values
MO Name in
Alarm Log
Alarm
Level
Initial SAT Command to Run
1
1. UU is the universal cabinet number listed in the PORT field of the Alarm or Error Log.
Full Name of MO
EMG-XFER MAJ test environment UU Emergency Transfer
EMG-XFER WRN test environment UU Emergency Transfer
Table 386: Emergency Transfer Error Log Entries
Error
Type
Aux
Data
Associated Test Alarm
Level
On/Off
Board
Test to Clear Value
0 0 Any Any Any test environment sh r
1
1 (a
) 0 Emergency Transfer Query
(#124)
MAJ ON test environment r 3
257 (b
) 0 Emergency Transfer Query
(#124)
WRN ON test environment r 3