EXP-INTF (Expansion Interface Circuit Pack)
Issue 1 June 2005 1227
1139 ABRT The packet bus in the PN where this EI circuit pack resides has a major
alarm against it. This test needs to use the alarmed port network’s packet
bus.
1. Enter display alarms and resolve any PKT-BUS alarms.
2. Retry the command.
1141 ABRT The Packet Interface circuit pack is out of service.
1. See PKT-INT (Packet Interface)
on page 1799 for the recommended
repair procedure.
1144 ABRT The PN’s packet bus has a major alarm against it. This test needs to use
the alarmed PN’s packet bus.
1. Enter display alarms and resolve any PKT-BUS alarms.
2. Retry the command.
1394 ABRT The EI circuit pack is out of service and the test cannot be run. This
condition is due to a change in the EI circuit pack’s ability to communicate
with the EI or SNI circuit pack on the other end of the fiber.
1. Run Test #237 and check the Error Log for EXP-INTF Error Type 1281.
If Error Type 1281 is present or if Test #237 does not pass, see the
repair procedures for Test #237, in Table 409: Test #237 Expansion
Interface Neighbor Query Test on page 1199.
2. If Test #237 passes, rest the EI pack. Note that this will not be
destructive to the port network where EI circuit pack resides because it
will not be serving as the expansion Archangel if it is not in service.
3. Repeat this test.
1395 ABRT This test cannot be run on an EI circuit pack if it is part of the B-side PNC
and duplicated PNC is not enabled.
1. If this test needs to run on this EI circuit pack, use change
system-parameters duplication to enable PNC.
2. Use set pnc lock to prevent the system from doing a PNC
interchange.
3. Repeat this test.
Table 416: Test #589 Expansion Interface Packet Interface Test (continued)
Error
Code
Test
Result
Description / Recommendation
3 of 5