Communication Manager Maintenance-Object Repair Procedures
2506 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
Test failure indicates failure of one or more of the following components:
VAL (TN2501) circuit pack
TDM bus
Tone generator / tone receiver circuit pack
Table 888: Test #1285 TDM Loop-Around Test
Error
Code
Test
Result
Description / Recommendation
1000 ABRT The port is in use.
1. Retry the command when the port is idle. You can force the port to the
idle state with busyout port location.
2. Escalate if the problem persists.
Note: This command is destructive, tearing down every call and link using
the port.
1002 ABRT No TDM bus timeslots available for the test.
1. Retry the command at 1-minute intervals up to 5 times.
2. Escalate if the problem persists.
1003 ABRT No more tone receivers idle for use in this test.
1. Retry the command at 1-minute intervals up to 5 times.
2. Escalate if the problem persists.
G700:
1412
ABRT On the G700, this test aborts with Error Code 1412.
2000 ABRT Did not receive circuit pack test response within the allowable time period.
1. If this problem persists, reset the circuit pack (busyout board
location, reset board location, and release board
location).
2. Repeat the test.
3. If the problem persists, replace the circuit pack.
2012 ABRT Internal system error.
1. Retry the command at 1-minute intervals up to 3 times.
2. Escalate if the problem persists.
2100 ABRT Could not allocate the necessary system resources to run test.
1. Retry the command at 1-minute intervals up to 5 times.
2. Escalate if the problem persists.