e. Error Type 125: No Aux Data: The wrong circuit pack is inserted in the slot where this
circuit pack is logically administered.
Remove the wrong circuit pack and insert the logically administered circuit pack
or
Re-administer this slot to match the circuit pack inserted (change circuit-pack).
f. Error Type 257: Associated with the Common Port circuit pack maintenance test. See
XXX-BD (Common Port Circuit Pack/Media Module)
on page 2539 for details.
g. Error Type 1538: hyperactivity on a circuit pack. Hyperactivity occurs when the angel is
sending too many CCMS messages uplink, 400 per ten seconds for the TN802B, to switch
software. The circuit pack will be taken out of service. See error Type 3999.
h. Error Type 2049: the operating system is down. An attempt is made to reset the board
automatically. If the reset fails, the board is probably bad and should be replaced.
i. Error Type 3841: Inconsistent downlink message. This error is not service-affecting. No
action is required.
j. Error Type 3999: the circuit pack sent a large number of control channel messages to the
switch within a short period of time.
If Error Type 1538 is also present, the circuit pack was taken out-of-service due to
hyperactivity.
If Error Type 1538 is absent, the circuit pack has generated 50% of the messages
necessary to be considered hyperactive but was not taken out-of-service. This may be
completely normal during heavy traffic periods.
If this error type is logged when the circuit pack is being lightly used, it may indicate a
problem with the circuit pack or the equipment attached to it.
System Technician-Demanded Tests:
Descriptions and Error Codes
Investigate tests in the order they are presented. By clearing Error Codes associated with the
Control Channel Loop test (#52), you may also clear errors generated from other tests in the
sequence.
Order of Investigation Short Test
Sequence
Long Test
Sequence
Reset Board
Sequence
D/ND
1
Control Channel Loop test (#52) X ND
SAKI Sanity test (#53) X D