OPS-LINE (DS1 Off-Premises Station Line)
Issue 1 June 2005 1739
1001 ABRT Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
1002 ABRT The system could not allocate time slots for the test. The system may be
under heavy traffic conditions or it may have time slots out-of-service
due to TDM-BUS errors. Use status health to determine if the
system is experiencing heavy traffic.
1. If the system has no TDM-BUS errors and is not handling heavy
traffic, repeat test at 1-minute intervals up to 5 times.
1003 ABRT The system could not allocate a tone receiver for the test. The system
may be oversized for the number of Tone Detectors present or some
Tone Detectors may be out-of-service. Use list measurements
tone-receiver to display information about the system’s tone
receivers.
1. Resolve any TTR-LEV errors.
2. Resolve any TONE-PT errors.
3. If neither condition exists, retry the test at 1-minute intervals up to 5
times.
1004 ABRT The test was aborted because the port was seized by a user for a valid
call. Use status station to determine the service state of the port. If
the service state indicates that the port is in use, then the port is
unavailable for certain tests. You must wait until the port is idle before
retesting.
1. Retry the command at 1-minute intervals up to 5 times.
1020 ABRT The test did not run due to an already existing error on the specific port
or due to a more general error on the circuit pack.
1. Examine the error log for existing errors against this port or the
circuit pack and attempt to diagnose the already existing error.
(Error code 1793 indicates a problem with the DS1 interface board,
and any problems on the associated DS1-BD or UDS1-BD should
be resolved first.)
G700:
1412
ABRT This test does not execute on a G700 media gateway.
Table 644: Test #6 NPE Crosstalk Test (continued)
Error
Code
Test
Result
Description / Recommendation