Mitsubishi Electronics QD77MS2 Home Security System User Manual


  Open as PDF
of 1038
 
3 - 8
Chapter 3 Specifications and Functions
Main functions Details
Reference
section
High-level positioning control
Block start (Normal start)
With one start, executes the positioning data in a random block with the
set order.
10.3.2
Condition start
Carries out condition judgment set in the "condition data" for the
designated positioning data, and then executes the "block start data".
When the condition is established, the "block start data" is executed.
When not established, that "block start data" is ignored, and the next
point's "block start data" is executed.
10.3.3
Wait start
Carries out condition judgment set in the "condition data" for the
designated positioning data, and then executes the "block start data".
When the condition is established, the "block start data" is executed.
When not established, stops the control until the condition is
established. (Waits.)
10.3.4
Simultaneous start
Simultaneously executes the positioning data having the No. for the axis
designated with the "condition data". (Outputs commands at the same
timing.)
10.3.5
Repeated start (FOR loop)
Repeats the program from the block start data set with the "FOR loop" to
the block start data set in "NEXT" for the designated number of times.
10.3.6
Repeated start (FOR
condition)
Repeats the program from the block start data set with the "FOR
condition" to the block start data set in "NEXT" until the conditions set in
the "condition data" are established.
10.3.7
Multiple axes simultaneous
start control
Starts the operation of multiple axes simultaneously according to the
command output level.
(Positioning start No. 9004, same as the "simultaneous start" above)
10.5
Manual control
JOG operation Outputs a command to servo amplifier while the JOG start signal is ON. 11.2
Inching operation
Outputs commands corresponding to minute movement amount by
manual operation to servo amplifier.
(Performs fine adjustment with the JOG start signal.)
11.3
Manual pulse generator
operation
Outputs pulses commanded with the manual pulse generator to servo
amplifier.
11.4
Expansion
control
Speed-torque control
Carries out the speed control or torque control that does not include the
position loop for the command to servo amplifier by switching control
mode.
12.1
Synchronous control
Carries out the synchronous control that synchronizes with input axis by
setting the system such as gear, shaft, change gear and cam to the
"synchronous control parameter".
12.2
In "major positioning control" ("high-level positioning control"), "Operation pattern" can
be set to designate whether to continue executing positioning data. Outlines of the
"operation patterns" are given below.
[Da.1] Operation pattern Details
Reference
section
Independent positioning control
(positioning complete)
When "independent positioning control" is set for the operation pattern of
the started positioning data, only the designated positioning data will be
executed, and then the positioning will end.
9.1.2
Continuous positioning control
When "continuous positioning control" is set for the operation pattern of
the started positioning data, after the designated positioning data is
executed, the program will stop once, and then the next following
positioning data will be executed.
Continuous path control
When "continuous path control" is set for the operation pattern of the
started positioning data, the designated positioning data will be
executed, and then without decelerating, the next following positioning
data will be executed.