Mitsubishi Electronics QD77MS2 Home Security System User Manual


  Open as PDF
of 1038
 
11 - 7
Chapter 11 Manual Control
11.2.2 JOG operation execution procedure
The JOG operation is carried out by the following procedure.
STEP 1
Preparation
Refer to Chapter 5
and Section 11.2.3.
End of control
STEP 2
Refer to Section
11.2.4.
STEP 3
Turn ON the JOG start signal.
STEP 4
Monitor using GX Works2.
STEP 5
Write the sequence program created in STEP1
and STEP2 to the PLC CPU.
Turn ON the JOG start signal of the axis to be
started.
Monitoring of the
JOG operation
Stop the JOG operation when the JOG start signal is turned
OFF using the sequence program in STEP 2.
STEP 6
Turn OFF the JOG start signal that is ON.
Monitor the JOG operation status.
Refer to Chapter 6.
JOG operation
start
JOG operation
stop
Set the parameters.
( to )
Pr.1
Pr.39
One of the following two methods can be used.
<Method 1>
Directly set (write) the parameters in the Simple Motion
module using GX Works2.
<Method 2>
Set (write) the parameters from the PLC CPU to the Simple
Motion module using the sequence program.
Create a sequence program for the following
setting.
Set a "0" in " Inching movement amount".Cd.16
Cd.17Set the " JOG speed". (Control data
setting)
Create a sequence program in which the "JOG
start signal" is turned ON by a JOG operation
start command.
QD77MS2/QD77MS4
Y8, YA, YC, YE
Y9, YB, YD, YF
Forward run JOG
start signal
Reverse run JOG
start signal
QD77MS16
Cd.181 Forward run
JOG start
Cd.182
Reverse run
JOG start
REMARK
Mechanical elements such as limit switches are considered as already installed.
Parameter settings work in common for all control using the Simple Motion module.