Mitsubishi Electronics TG-2000A Air Conditioner User Manual


 
92
8.12 Watt Hour Meter Set-Up (For RS-485)
Set the connection to the watt hour meter.
WHM setup sets the serial ports which connect to watt hour meters and the number of watt hour meters,
address, WHM name, and maximum integrated value. It can be set for With WHM connection only.
Refer to section 8.8.4 for the measurament meter for PI controller.
8.12.1 Setting Procedure and Restrictions
Before setting or changing WHM, check the precautions.
Check before WHM setup.
[Procedure]
1) Click [Watt hour meter set-up] button.
From the Initial window, click on the [Watt hour meter
set-up] button in the System Settings group.
2) Click [OK] button after checking the display contents.
If there is no problem when the contents of the alarm
displayed are checked, click the [OK button.
* If the [Cancel] button is clicked, the settings are interrupted
and the screen returns to the initial window.
The Watt hour meter set-up are done in the following order.
Step 1 Watt hour meter setting
Step 2 Set-up for the name and the maximum integrated value of WHM
8.12.2 Watt Hour Meter Setting (Step 1)
Set the connection to the watt hour meter.
1) Select the port to assign to the watt hour meter.
Click the watt hour meter option button, and set the
serial port to be used.
2) Select the watt hour meter name.
Select a name to be assigned to the watt hour meter.
3) Set the number and address of the watt hour meters.
Set the number of watt hour meters to be used and
their address.
4) Set the serial No.
Input the serial No. for Model AEM31D/485 only.
Example) When S/N 70-87948, set 87948.
5) Select [OK] button.
When finished making changes, click the [OK] button.
* If the [Cancel] button is clicked, the settings are interrupted and
the screen returns to the initial window.
When address setting and communication confirmation
failed, a warning message is displayed. Check the set
contents.
Watt hour meter set-up preparation screen
Watt hour meter setting screen
Warning screen
Maintenance Tip (Caution)
When changing the contents of settings related to the energy monitoring functions, be sure to compile
(date specification) the charge information up to the previous day and print it out or have the result in
hand before making changes to the settings. If charge information is not processed, the charge
information will not be apportioned correctly.
The monthly bill consists of a) + b) + standard charge
a) Charge information from the start of the current charge period to the day prior to any changes
b) Charge information from the day after any changes to the end of the current charge period
There may be a discrepancy in the charge information just before or after a change to these settings.
* For details on setting charge periods, refer to Management manual section “9.3 Air-Conditioning Charge Output”