118
8.17.2.3 Peak cut setting (Step 2)
Monitor the peak cut details set in the AG-150A/G-50A.
1) Click the [Monitor] button.
If peak cut is already set, the set details will appear in
the window.
Select the AG-150A/G-50A for peak cut control
1) Select the AG-150A/G-50A No. with the
button.
Select the AG-150A/G-50A for peak cut control by
clicking
.
Batch setting for the “Whole building”
If "Whole building" is selected and not all AG-150A/G-50A units are set to the same settings, those
fields that have different settings for different AG-150A/G-50A units will appear blank.
If it is not necessary to change the setting for any item, leave the item blank as it is.
To change the settings, select an appropriate option for the blank field.
In the case of TG-2000A Ver 5.10 or earlier and Ver. 5.20, the fields cannot be left blank. Change the settings so
that the settings for all G-50A will be the same.
Set the control start electric amount
1) Set level 1 with the /
buttons.
Set the level 1 control start electric amount with the
/
buttons.
2) Set levels 2 to 4 with the /
buttons.
Set the control start electric amount for levels 2 to 4
with the
/
buttons.
Set the peak cut function for the indoor units
1) Select the operation block to be set for each
level with the
button.
Select the operation block to be set for each
level by clicking
.
The number of levels set with the control start
electric amount can be set.
2) Select the control details with the
button.
Select the control details for energy saving operation by clicking
.
Control details: No control
Temperature control
Ventilator operation (Thermo OFF)
Operation stop
3) Select the control time with the
button.
Select the control time for energy saving operation by clicking
.
The following times can be set when a setting other than "No control" is selected for the control details.
Control time: 3 minutes
6 minutes
9 minutes
15 minutes
30 minutes
4) Repeat steps 1) to 3).
Repeat steps 1) to 3) for the operation blocks set for energy saving.
Peak cut setting screen
Note:
• By setting "Whole building" for AG-150A/G-50 No.,
all operation blocks (outdoor units) can be set to
energy saving in a group.