Mitsubishi Electronics TG-2000A Air Conditioner User Manual


 
62
8.6 AG-150A/G-50A Connection Set-up
Set the integrated centralized control softwareTG-2000A, number of AG-150A/G-50A units connected,
and the IP address. It is possible for this setting to monitor and display the option functions state of the
AG-150A/G-50A.
8.6.1 Setting Procedure and Restrictions
Confirm the precautions and procedure before setting the AG-150A/G-50A connection.
Perform the check before setting the AG-150A/G-50A connection.
[Procedure]
1) Select the [AG-150A/G-50A connection set-up] button.
Click the [AG-150A/G-50A connection set-up] button
located in the system setting group on the initial
window.
2) Select the [OK] button after confirming the display
contents.
Check the contents of the alarm displayed. When
there are not any problems found, click the [OK]
button to advance to the setting.
* When the [Cancel] button is clicked, this setting is
terminated to return to the initial screen.
Set the AG-150A/G-50A connection in accordance
with the following procedure.
Step 1: Number of AG-150A/G-50A set-up
Step 2: IP address of AG-150A/G-50A set-up
8.6.2 Number of AG-150A/G-50A set-up (Step 1)
Set the number of AG-150A/G-50A connected to the
system.
Set-up the number of AG-150A/G-50A
[Procedure]
1) Click the
/
buttons.
Use the “
/
“ buttons to set the number of
AG-150A/G-50A.
* Values can also be input from the keyboard.
Number of connectable G-50A units: 1 to 40 units
2) Click [OK] button.
When finished making settings, click the [OK] button.
* When the [Cancel] button is clicked, this setting is
terminated to return to the initial window.
8.6.3 IP address of AG-150A/G-50A set-up (Step 2)
Set the data of the AG-150A/G-50A IP address
connected to the data of the integrated centralized
control software.
Register the AG-150A/G-50A IP address.
[Procedure]
1) Select the AG-150A/G-50A No. with the “
/
buttons.
In this case, use the “
/
“ buttons to select the
AG-150A/G-50A No. for which the IP address
information is registered.
2) Set the IP address.
Input the IP address for the number of
AG-150A/G-50A units to be connected.
Set the IP address for the number of AG-150A/G-50A
units connected.
AG-150A/G-50A connection Set-up
Number of AG-150A/G-50A Set-up
IP address of AG-150A/G-50A set-up