8.3.4 Energy Saving /Peak Cut and IC I/O Sigmal/Interlocked Control Setting
Set the energy saving settings/peak cut function and
trend functions
Set whether the other functions are valid.
[Procedure]
1) Click the option button.
Select the energy saving/peak cut function settings
with the option button.
Item Set value Details
Deactivate Energy saving/peak cut function disabled. (Default)
Energy saving Energy saving function enabled.
Peak cut (WHM) Peak cut function with WHM enabled. (Including energy saving function)
Energy saving/
peak cut
function *1
Peak cut (PLC) Peak cut function with demand controller connected to PLC (Including
energy saving function)
Deactivate Do not connect general equipment to IC I/O signal. (Default)
Interlocking control will not be performed on PLC for general
equipment.
IC I/O signal
/interlocking
control function
*2
Activate Connect general equipment to IC I/O signal for monitoring and operation.
Interlock control will be performed on PLC for general equipment.
*1: There are two types of peak cut functions.
WHM: The power rate is read in from the electric amount count PLC or PI Controller, and the level is
judged by the AG-150A/G-50A.
PLC for demand input: A demand controller is connected to the PLC for demand input, and the PLC for demand
input which receives contact signals according to the level notifies the AG-150A/G-50A.
*2: When interlocking control, such as stop of the air conditioner, is performed on PLC for general equipment while the
general equipment (e.g. card key) is ON, “Activate” must be set.
8.3.5 Energy Monitoring Related
Follow these steps to energy monitoring functions On or Off, automatically print air conditioning
charges, and set printing options.
Energy monitoring functions On or Off
[Procedure]
1) Click the option button
Use the option button to select Energy
Monitoring function, Automatic Air Conditioning
Charges Print, or Air Conditioning Charge Output
Processing function setup.
Note:
The "Peak cut function" cannot be selected when the PLC watt hour meter or PI Controller, is no
t
connected.
The "Energy saving function" and "Peak cut function" license numbers must be registered in the
G-50A to use the energy saving function and peak cut function.
Peak Cut, etc. functions
Energy monitoring related