Mitsubishi Electronics TG-2000A Air Conditioner User Manual


 
17
Updating the AG-150A
Monitor the system for the target AG-150A.
Step Item Details
1 Connect the LAN cable Connect the AG-150A and computer with the LAN.
2
Set the Update Program
CD for AG-150A
Insert the Update Program CD (for AG-150A) in the computer's
CD-ROM drive.
3 Start the Monitor tool Update screen will be displayed automatically.
4
Input the IP address, and
start the Monitor
Input the IP address on the Monitor window, and then press the
[Start Monitor] button.
5 Complete the Monitor
The Monitor is completed when the progress graph reaches
100%.
Updating the G-50A
Monitor the system for the target G-50A.
Step Item Details
1 Connect the LAN cable Connect the G-50A and computer with the LAN.
2
Set the Update Program
CD for G-50A
Insert the Update Program CD (for G-50A) in the computer's
CD-ROM drive.
3 Start the Monitor tool Update screen will be displayed automatically.
4
Input the IP address, and
start the Monitor
Input the IP address on the Monitor window, and then press the
[Start Monitor] button.
5 Complete the Monitor
The Monitor is completed when the progress graph reaches
100%.
[Operation environment]
A computer containing the integrated centralized control software TG-2000A can be used, but
when updating the system with a different computer, make sure that the computer satisfies the
following operation environment.
Table AG-150A/G-50A Monitor computer operation environment
Item Details
OS Windows Vista/XP/2000
CPU Pentium® 133MHz or faster (The required CPU speed depends on Windows
(OS).)
Memory 64Mbyte or more (The required memory size depends on Windows (OS).)
Built-in LAN port or LAN card One
Others CD-ROM drive (required for installation), mouse or other pointing device
Note:
If a communication error occurs while updating the system, the AG-150A/G-50A will
standby in the Monitor mode for ten minutes. Click on the [Start Monitor] button again to
restart the Monitor.
The license for the “Web monitor” must be registered from the AG-150A unit.
Take the following measures if update fails and the system does not startup properly.
[G-50A]
Turn the power to the G-50A back on with buttons [1] and [0] on the G-50A unit being
held down, and keep them held down for 10 more seconds. G-50A will start up in the
Update mode. Follow the instructions on the screen and try performing an update
again.
[GB-50A]
Turn SW 1-1 and 1-2 on the GB-50A unit, and then turn the power on. G-50A will start
up in the Update mode. Follow the instructions on the screen and try performing an
update again.
After the update, turn the service switch SW1 to OFF, and reboot the unit.