9.4 Charge Parameter Output
This function is used to output the operation amount data (integrated capacity save ratio of indoor unit,
integrated FAN operation time, integrated thermo-ON time, (integrated auxiliary heater operation
time)) and charge parameters to the file.
Output the operation amount data, which is the charge parameters, to the file.
[Procedure]
1) Select [charge parameter output] menu.
Select the [charge parameter output] located in the
[Tool] menu in the initial window where the charge
parameter output screen is displayed.
* Note that this screen cannot be selected in the Management
screen.
2) Select the output target
Click and select the PLC or AG-150A/G-50A for the
output unit type with the output selection “
button.
3) Set the interval.
Use the “
/
” buttons to set the year, month, and
day of the objective interval. An interval from the
previous day to 122 previous days can be set.
* The setting is executable regardless of whether the data for the
date concerned exists or not.
4) Set the file output destination.
Set the file output destination folder. An existing folder can be selected by clicking the [Select] button.
5) Set the save filename and click the [Output] button.
After setting the output destination and file name, click the [Output] button. The file is saved. After
finishing, this screen closes.
* Click the [Cancel] button to return to the Initial window.
Note:
The value stored in PC of TG-2000A is output unchanged. Contact us separately for the data
generation method and other information.
* The values of the capacity save ratio, FAN operation time, thermo-ON time, and auxiliary heater operation time are
integrated values. When the value exceeds “9999.99”, it is returned to “0000.00”.
* The meter data is integrated values. When the value exceeds “999999.99”, it is returned to “000000.00”.
The file output is executed for each AG-150A/G-50A.
The data for only up to 122 days from the previous day is saved. Data other than the saved data
cannot be output.
Note:
When a nonexistent folder is described as the file output destination and the [Output] button is
clicked, the file is saved by creating a new folder.
-
-
Char
g
e paramete
r
output
(
se
t
up
)
screen
A
G-150A/G-150A select button
Out
p
ut term settin
g
Out
p
ut file name settin
g
Note:
The monitor of the operation amount/electric amount data is intended for all indoor units for the
object day, in which the contents are written over the PC database on which the integrated
centralized control software (TG-2000A) operates. Monitor only the necessary date.
Monitor the data for the last day after 7:00. (Monitor after 9:00 only when using the heat
storage model.)
Even if the operation amount/electric amount data monitor is executed, it cannot use the results
for the recalculation of proportionally divided power charges. In this case, use the “Maintenance
of charge data” shown in section 9.2 or the “Charging remedy” shown in section9.5.
Note that the data is not reflected in the “Maintenance of charge data” screen even if the
operation amount/electric amount data is gathered using this function, but upon the output o
f
the charge parameter data.