112
8.17 Energy Saving/Peak Cut Set-up
Set the energy saving and peak cut.
The AG-150A/G-50A for energy saving operation, the control state of the indoor units in each
operation block, and the control status of each outdoor unit is set for energy saving. The watt hour
meter subject to the control measurement and the control status at each level is set for the peak cut
setting. The peak cut function can be set only when a watt hour meter/meter connection is enabled
and the air conditioner watt hour meter is connected.
Table Energy saving and peak cut setting items
Item Setting details Remarks
Block Contents of control No control, temperature control, ventilator/
thermo OFF control, stop control
Control time (*1) 3 min., 6 min, 9 min, 15 min, 30 min. Select only when control is valid
The difference of
temperature (*2)
Deactive, Active (1°C unit between 3°C
and 9°C)
Select only when control is valid
Contents of control No control, performance save rate
(90%, 80%, 70%, 60%)
Outdoor
unit
Control time 3 min., 6 min, 9 min, 15 min, 30 min. Select only when control is valid
*1: Set the time to control for 30 minutes.
*2: The "The difference of temperature" disables the energy saving (level 0) control if the temperature exceeds the
difference of the set temperature and intake temperature during energy saving (level 0).
8.17.1 Energy saving setting
8.17.1.1 Setting Procedures and Restrictions
Before setting or changing the energy saving function, check the precautions.
Preparing to set the energy saving function
[Procedure]
1) Click the [Energy Saving] button.
From the initial window, click on the [Energy Saving]
button in the System Settings group.
2) Click the [OK] button after checking the display
contents.
Check the details displayed in the warning, and then
click the [OK] button.
* If the [Cancel] button is clicked on, the settings will be
canceled and the initial window will open
.
The energy saving function is set in the following
order.
Step 1 Energy saving setting
8.17.1.2 Energy saving setting (Step 1)
Monitor the energy saving details set in the AG-150A/
G-50A.
1) Click the [Monitor] button.
The energy saving details already set will appear in
the window.
Set the AG-150A/G-50A for energy saving control
1) Select the AG-150A/G-50A No. with the
button.
Select the AG-150A/G-50A for energy saving control
by clicking
.
Note:
• By setting "Whole building" for AG-150A/G-50 No.,
all operation blocks (outdoor units) can be set to
energy saving in a group.
Energy saving setting preparation screen
Energy saving setting screen