Mitsubishi Electronics TG-2000A Air Conditioner User Manual


 
124
8.20 Time Set-up
The time set-up function comes in two types, date/time set-ups and time monitor set-ups.
Function Contents
Date/time set-up Sets the date/time of all AG-150A/G-50A units and PLCs connected to the
computer as soon as the PC date/time is set.
* Be sure to set the current time on AG-150A/G-50A and PLC at the initial settings
before starting the operation.
Time monitor Confirms the difference in time between the time reference machine
(AG-150A/G-50A No.1) of this system and all AG-150A/G-50A units and PLCs
except for No. 1 and the PC.
* PC means a computer on which the integrated centralized control software TG-2000A operates.
Set the date/time.
[Procedure]
1) Select [Time set-up] button.
Click the [Time set-up] button located in the system
setting group on the initial window.
2) Select the [Date/time set-up] button.
Click the [Date/time set-up] button on the time set-up
select screen.
3) Select the part you want to change.
Click “Year”, “Month”, “Day”, “Hour”, “Minute”, or
“Second” you want to change.
4) Select the “
/
button.
Use the “
/
” buttons to change the numbers of
the part to be changed.
5) Click [OK] button after finishing all settings.
When done with these settings, click the [OK] button.
* When the [Cancel] button is clicked, this setting is terminated
to return to the initial window.
Note:
The alarm message shown in the following
illustration is displayed when the [Date/time
set-up] button is clicked.
OK : Displays the date/time set-up screen.
Cancel : Returns to the system set-up screen
without displaying the date/time set-up.
Time set-up select screen
Date/Time set-up screen
Time Change Not Allowed dialog box
<Precautions for using this function>
Basically with this system, the time does not need to be adjusted manually, except for the first time.
(Excluding when correcting an error in the time.) When using the power apportioning billing function, do
not adjust the time needlessly.
Never change the date after starting the power apportioning billing function.
[Description]
With this system, the air conditioner operation data is collected from the AG-150A/G-50A main unit and
the electric amount data is collected from the PLC. The air-conditioning charges are calculated based on
this data using the various amounts and unit prices set in this integrated centralized control software
(TG-2000A). When there is a difference in time between the PLC or AG-150A/G-50A main unit and PC
on which the integrated centralized control software TG-2000A operates, it becomes unable to correctl
y
execute the calculation.
Thus, TG-2000A, AG-150A/G-50A and PLC times are adjusted each day to correct any time erro
r
between the devices. (The time adjustment is based on the No.1 AG-150A/G-50A.)