113
Batch setting for the “Whole building”
If "Whole building" is selected and not all AG-150A/G-50A units are set to the same settings, those
fields that have different settings for different AG-150A/G-50A units will appear blank.
If it is not necessary to change the setting for any item, leave the item blank as it is.
To change the settings, select an appropriate option for the blank field.
In the case of TG-2000A Ver. 5.10 or earlier and Ver. 5.20, the fields cannot be left blank. Change the settings so
that the settings for all G-50A will be the same.
Set the energy saving function for the indoor units
1) Select the operation block to be set with the
button.
Select the operation block to be set by clicking
.
2) Select the control details with the
button.
Select the control details for energy saving
operation by clicking
.
Control details: No control
Temperature control
Ventilator operation (Thermo OFF)
Operation stop
3) Select the control time with the
button.
Select the control time for energy saving operation by clicking
.
The following times can be set when a setting other than "No control" is selected for the control
details.
Control time: 3 minutes
6 minutes
9 minutes
15 minutes
30 minutes
4) Repeat steps 1) to 3).
Repeat steps 1) to 3) for the operation blocks set for energy saving.
Set blocks excluded from energy saving operation
5) Select the excluded functions with the
button.
Select the whether functions are excluded from energy saving operation by clicking the
button.
6) Select the excluded temperature difference with the
button.
Select the conditional temperature difference to be excluded from energy saving operation by
clicking
.
Setting temperature difference: 3 deg. to 9 deg. (1 deg. increments)
Setting the energy saving function for the outdoor unit
1) Select the outdoor unit to be set with the
button.
Select the outdoor unit to be set by clicking
.
If “OC” is selected on the Option under Unit,
outdoor units other than A-control models can be
selected (Outdoor unit addresses will be
displayed.)
If “AOC” is selected, A-control models of
outdoor units can be selected (The outdoor unit
addresses and the group names will be displayed.)
Note:
• The target indoor units are displayed in the "Control group" field.
• If the settings are the same for each block, use the "Copy" and "Paste" functions to make the process
easier.
Note:
• These settings excluded from energy saving operation are batch settings for each AG-150A/G-50A.
• “Temperature difference” means the difference between the suction temperature and the set
temperature during cooling and the difference between the set temperature and suction temperature during
heating. If the degree of temperature difference exceeds the preset value, the unit will be excluded from th
e
energy save control to maintain the comfort level.
1)
2) 3)
5) 6)
1)
2) 3)